27K TRI ZONE OUTDOOR CONDENSING UNIT - DUCTED SYSTEM 21 SEER2
27K TRI ZONE OUTDOOR CONDENSING UNIT - DUCTED SYSTEM 21 SEER2
SKU: CMZ-27-3Z
PRODUCT TYPE: Multizone Condensing Units
Refrigerant Type:
R410a
SEER2:
21
EER2:
11.5
HSPF2-4:
9.2
HSPF2-5:
7.0
Max. Allowable Piping Length (ft):
82 for 1 IDU for 148 sum up
Min. Allowable Piping Length (ft):
9.8
Max. Allowable Elevation Differences (ft):
33 for ODU higher than IDU, 49 for ODU lower than IDU, 33 between IDU and IDU
Min. Power Supply Wire Size (AWG):
12*3
Min. Inter-Connecting Wire Size (AWG):
16*4, Stranded
Piping Size:
(1/4"-3/8")*3
Operating Mode:
Heating and Cooling
Outdoor Ambient Temperature:
-13°F
Outdoor Unit Net/Gross Weight (lbs.):
139.77/150.57
Features
Features
Flex-mount Multi-zone Heat Pump Outdoor Units 9,000 - 18,000 Btu/h.
• Inverter Technology • Factory Pre-Charge (25 ft.) • Slow Ambient Operation to -13°F • Self-Diagnostics • Energy Efficient • Simple installation. • All indoor units can be controlled individually.
Available Indoor Units:
- Fan Coil
- AHU
Specifications
Specifications
Unit Size - Inches (W x D x H): 37.24x16.14x31.89
Voltage: 208-230V
Air Flow - CFM (Hi / Mi / Lo): 2129.41
Tonnage: 2.25
dB(A) Noise Level (Hi / Mi / Lo): 61
Heat Capacity (BTU): 28000
Cooling Capacity (BTU): 28000
Placement: Tri Zone Outdoor Unit
Breaker Size (A): 35
Factory Refrigerant Charge (ft): 25*3
Refrigerant Adjustment Factor (oz. per ft): 0.16
Drain Pipe Size (in): refer IDU
Free Lift Gate
*This product qualifies for Free Lift Gate Service. Items over 100lbs normally ship via semi-truck. Select this service if you need the product lowered to the ground curbside.(Must always have installed a minimum of 2 Indoor Units)